§ 36-99. POTW protection criteria.
Latest version.
No user shall discharge wastewater containing in excess of the following POTW protection criteria concentrations without prior notification and approval from the city. These average concentrations apply at the point where the wastewater is discharged to the POTW collection system. The City of Mebane has the right to establish additional POTW protection criteria at any time it is deemed necessary,
Ammonia 25 mg/l BOD 300 mg/l COD 750 mg/l Chloride 40 mg/l Fluoride 1.5 mg/l Phosphorus 7.0 mg/l TSS 300 mg/l Aluminum 2.5 mg/l Arsenic 0.01 mg/l Cadmium 0.002 mg/l Chromium (total chromium) 0.005 mg/l Copper 0.05 mg/l Cyanide 0.005 mg/l Lead 0.01 mg/l Mercury—Contact POTW
for current mercury limit. <0.0002 mg/lMolybdenum 0.005 mg/l Nickel 0.01 mg/l Selenium 0.01 mg/l Silver 0.01 mg/l Zinc 0.20 mg/l
(Ord. No. OA-13-02, § 2.3, 9-3-2013)